Feature:
1. Hall‑type current conversion, which can withstand 30 times the nominal input, prevents instantaneous high current access and burns out the internal components of the sensor. The measurement circuit is isolated from the incoming signal
2. Isolate the detection signal and the output signal, effectively filter the noise in the signal, which will greatly improve the signal‑to‑noise ratio and signal stability of the product, and effectively enhance the product s anti‑interference ability
3. The primary and secondary sides of the hole current transmitter are highly insulated and isolated, which bring high accuracy, small size, low power consumption, wide frequency response, and anti‑interference
4. No insertion loss because of erforated input, fixed with standard guide rail and flat screws, easy to install
5. Especially suitable for load current intelligent monitoring systems such as generators, motors, intelligent low‑voltage power distribution cabinets, air conditioners, fans, street lamps, power grid monitoring, motor signal monitoring, railway system signal monitoring industries
Specification:
Item Type: AC Current Transmitter
Material: ABS
Power Supply: DC24V
Installation Method: Standard rail + flat screw fixation
Product Use: Used to measure AC current, especially for power frequency 50Hz sine wave AC current
Rated Current: AC0 100A
Rated Output: DC4 20mA
Load Capacity: Voltage Output: 5mA; Current Output: 6V
Accuracy: 0.5percent
Overload Capacity: 30 Times the nominal input
Isolation withstand Voltage: 3KV 50Hz, 1Min
Offset Voltage: less than 10mV
Temperature Drift: less than 500PPM celsius
Linearity: 0.1percent
Frequency Bandwidth: 20 5KHz
Current Consumption: <15mA+ output current
Response Time: <200ms
Working Temperature: 109 celsius +70 celsius
Storage Temperature: 25 celsius 85 celsius .
Package List:
1 x AC Current Transmitter
Note:
Please do not use 250ohm or 500ohm to connect 4‑20mA output version of the transmitter to get 0‑5V or 0‑10V, this is a completely wrong method, you cannot get 0‑5V or 0‑10V signal, and it will make transmit becomes overheated or damaged.